4. a) Input Power Factor Correction Sub-System : ( For Pro901 & Pro902 )
The purpose of power factor correction (P.F.C.) circuit is to make a constant bus for
Inverter in Buck and Boost mode. The schematic is indicated in figure 8.
When the input AC power cord is plugged in, the AC relay is activated and the AC
power goes through noise filter to the charger and to the line detector. Both DC buses
present voltages at about 1.4 times of input RMS voltage. When the UPS is in Buck or
Boost mode, the P.F.C. circuit is enabled and the DC bus is regulated at 360 Vdc.
4. b) Input Power Factor Correction Sub-System : ( For Pro903 )
The purpose of power factor correction (P.F.C.) circuit is to make the input current
and voltage in phase and therefore achieve a high input power factor near to 1. The
schematic is indicated in figure 7.When the input AC power cord is plugged in, the AC
relay is activated and the AC power goes through noise filter to the charger and to the
line detector. Both DC buses present voltages at about 1.4 times of input RMS voltage.
When the "on" switch is pressed, the P.F.C. circuit is enabled and the DC buses are
regulated at ±360 Vdc.