UPS Sizing



UPS Rating = 3000VA = 3 KVA                    
Daya beban = 3000VA x 0.8 = 2400W.
Output Load Power = 2400 Watt.
* 0.8 = power factor         

Number of  for 3KVA = 6 Block/pcs.       



     
inverter efficiency    = 0.85               
Battery End Voltage per block     = 10.2    VDC        

   
DC Power     = Output Load Power / inverter efficiency   
                   =  2400    /  0.85   
                   =  2824               
Power yang di butuhkan tiap Blok battery
= DC power / Number of battery   
= 2824 /    6   
= 471 Watt or       
= 46A    

catatan : 
46 A untuk menentukan :
 - total arus yang mengalir ke batterei secara keseluruhan.
 - Ampere NCB batterei (log run model).

untuk menentukan backup- time  ups, perhitungan sederhana sbb :
( voltage  x Ampere ) batterei = ...watt   x 0.8 (effeciency inverter).
contoh : batterei 8,2AH 12 Volt. Jadi real daya batterei = (12x 8.2AH)x0.8 = 78,72 Watt .
berapa lama backup time untuk 1 camera ip .
ipcamera =12 volt 0.5A             