UPS Rating = 3000VA = 3 KVA
Daya beban = 3000VA x 0.8 = 2400W.
Output Load Power = 2400 Watt.
* 0.8 = power factor
Number of for 3KVA = 6 Block/pcs.
inverter efficiency = 0.85
Battery End Voltage per block = 10.2 VDC
DC Power = Output Load Power / inverter efficiency
= 2400 / 0.85
= 2824
Power yang di butuhkan tiap Blok battery
= DC power / Number of battery
= 2824 / 6
= 471 Watt or
= 46A
catatan :
46 A untuk menentukan :
- total arus yang mengalir ke batterei secara keseluruhan.
- Ampere NCB batterei (log run model).
untuk menentukan backup- time ups, perhitungan sederhana sbb :
( voltage x Ampere ) batterei = ...watt x 0.8 (effeciency inverter).
contoh : batterei 8,2AH 12 Volt. Jadi real daya batterei = (12x 8.2AH)x0.8 = 78,72 Watt .
berapa lama backup time untuk 1 camera ip .
ipcamera =12 volt 0.5A